GPS3000 (2400kW)

gps3000_package

The GPS3000 is ideal for facilities that require high quality and highly reliable standby (or emergency) power generation and a capacity from 2000 kW to 2400 kW.  The GPS stand-by gas turbine is designed for reliable emergency back up power for data centers, hospitals (non-life safety loads), prisons and other mission critical facilities.

gps3500_engine

A Closer Look

The GPS units start and accept full power in 30 to 40 seconds. The GPS units are approximately 50% the weight and footprint of a comparably sized diesel engine generator, so they are well suited for installation on rooftops or mezzanines, saving valuable real estate for other purposes.  The GPS unit can operate on natural gas, kerosene and diesel fuel, and can switch automatically between fuels during operation at 100% power output.

More GPS Series Gas Turbines
Download More Information

Unit Specifications - IP Units(Switch To SI Units)
Unit Configuration Electric Output Fuel Consumption (Diesel) Dimension (L x W x H) Weight
kWe gph inches lbs
Outdoor 2,400 329 347 x 99 x 178 59,870
Indoor 2,400 329 278 x 99 x 146 55,240


Fuel:
Liquid (Diesel / Kerosene), Natural Gas or Dual Fuel (with automatic switching between the dual fuels)

Note:

Performance based upon the following:

Power output from ambient temperature of 41 oF to 104 oF [5 oC to 40 oC]

Fuel consumption at ambient temperature of 59 oF [15 oC]

Elevation of 492 feet [150 m] above sea level

Natural gas supplied to unit at 200 psig


Standard Equipment Special Features
  • Reduction gearbox with main lube oil pump and turning motor
  • VFD soft start - motor starting system
  • Indoor enclosure with maintenance doors, sound attenuated to 85 dBA, with lighting system, and fan forced ventilation,
  • 4160 V generator , open drip proof design, air cooled, with brushless PMG exciter
  • Heavy-duty I beam steel base-frame for the turbine engine, primed and painted
  • Lube oil system includes gear driven main lube oil pump, simplex filter, air cooled lube oil heat exchanger, static vent demister, tank integrated into the base-frame with oil heater
  • Liquid fuel system with gear box driven fuel oil pump.
  • Fire and gas detection with CO2 fire suppression system
  • State-of-the-art PLC control - Allen Bradley
  • Engine Removal compartment Eye hooks with chain fall lift
  • Battery system (lead acid) with battery charger for coast down lube oil pumps and jacking motor
  • Exhaust flex joint with exhaust ducting
  • Proven Heavy Duty Industrial Design
  • High Efficiency
  • 40 second start to full load operation
  • Option: High pressure air start
  • Option: Ni-cad battery system
  • Option: Output voltage ranging from 4.16 kV to 6.6 kV (60 Hz) or 3.3 kV to 6.6 kV (50 Hz)