Ideal for reliable emergency backup power ranging from 2200 to 2400 kW's. Ideal for dual fuel operation on either oil or gas fuels. The GPS3000 is ideal for emergency back up power for use in: data centers, shopping malls, industrial process plant applications, hospitals, universities, office complexes , pharmaceuticals, LNG Terminals, and other facilities. Our GPS units go from start to full load in 40 seconds. Compared to diesel gen sets our units are lighter and can be roof mounted freeing up valuable land for other uses. Also our GPS units can burn natural gas fuel, eliminating the need for fuel oil tank installations on site. |
|
A Closer Look
The GPB3000 is designed for emergency back up electric generation use in ; Data centers, shopping malls, industrial process plants, Hospitals, Universities/ colleges , large office complexes and apartment/condo complexes incorporating CHP - district heating and cooling systems, pharmaceuticals, LNG Terminals, city subway systems, and other industrial facilities. Unlike heavy diesel generator sets - our GPS units are light weight and can be roof mounted freeing up valuable commercial land for other uses. Unlike diesel gen sets our units can also burn natural gas - ( or both) eliminating the need to install cumberson fuel oil tanks on site. Our GPS units go from start to full load in 40 seconds.
|
More GPS Series Gas Turbines
Download More Information |
| 100% Load Condition Data - US Customary Units (Switch To Metric) | ||||||
| Electric Output | Dimension (L,W,H) | Heat Rate | Weight | Exhaust Gas Temp. | Exhaust Gas Flow | |
| kWe | ft | Btus/kW-hr | lbs | °F | lbs/hr | |
| 2,400 | ||||||
| Units Weights and Dimensions - US Customary Units (Switch To Metric) | |||||
| Electric Output | Dimension (L,W,H) | Weight | Exhaust Gas Temp. | Exhaust Gas Flow | |
| kWe | feet | lbs | °F | cu ft /hr | |
| 2,400 | 18 X 7.8 W X 9 | 41,600 | 1094 | 74,500 | |
Fuel:
Liquid fuel system burning diesel fuel is our standard unit configuration
Dual fuel system with natural gas fuel is available along with air start system for black start.
Note:
Performance based on 4 inch and 10 inch H2O intake / exhaust pressure losses
Sea level site
|
Standard Equipment
|
Special Features
|