Ideal for base load electric generation from 2 to 3 MW's in areas requiring a Green engine with reduced engine emissions. The GPB30D packged power plant, utilizes Kawasaki's Dry Low Emissions combustion sytem technology to assure reduce emissions. This unit offers electrical efficiency of 30% and an overall Cogeneration thermal efficiency of 80%. It is ideal for use in areas requring base load operation and reduced engine emissions in the 2 to 3 Mw power range. This GT unit is designed for use in: industrial process plant applications, Ethanol plants, Hotels, Data centers, Shopping malls, Hospitals, Universities, Office and apartment- condominium complexes with district heating and cooling loads, Pharmaceuticals, LNG Terminals, City electric rail and subway sytems, and other facilities with significant thermal and electrical loads. |
|
A Closer Look
The GPB30D is ideal for use in areas requiring low engine emissions in regulated emissions areas. Electric power canbe proivded to either 50 or 60 Hz systems. Applications include: Shopping malls, industrial process plants, hospitals, universities / colleges, office and apartment complexes incorporating district heating and cooling loads, pharmaceuticals, City electric rail and subway systems, LNG Terminals, and other facilities with significant thermal and electrical loads. |
| 100% Output performance Data w/ CHP Output - US Customary Units (Switch To Metric) | |||||||
| Inlet Air Temp. | Power | Fuel consumption | Exhaust Temp. | Exhaust Flow | HRSG Steam | CHP Efficiency | |
| F | kW | kW | °F | lbs/sec | lbs/hr | % | |
| 59 | 2,850 | 12,144 | 993 | 17.6 | 22,660 | 77.0 | |
| 32 | 3,242 | 13,243 | 960 | 19 | |||
| 86 | 2,500 | 11,140 | 997.5 | 16.3 | |||
| 95 | 2,372 | 12,830 | 1007 | 15.9 | |||
| Units Weights and Dimensions - US Customary Units (Switch To Metric) | ||
| Dimension (L,W,H) | Weight | |
| inches | lbs | |
| 234 L x 94W x 92H | 48,600 | |
Fuel:
Natural Gas fuel , NOx Reduction: Dry Low Emission, NOx: 23 ppm, CO: 25 ppm, VOC: 2.0 ppm
Note:
Performance based on 4 inch and 10 inch H2O intake / exhaust pressure losses
DLE is available from 50–100% load
Sea level site
Required gas pressure: 206 psig
* Contact Kawasaki Application Engineering for site-specific performance
* Not for guarantee
|