Ideal for reliable power generators requiring from 400 to 500 kW's The GPS500 is ideal for 400 Kw power systems requiring dependable back up emergency power. It is ideal for use in: Data centers, industrial process plants, Hospitals, Universities, office and apartment buildings, pharmaceuticals, communications centers - This design can burn either liquid or natural gas fuels and can start and attain full load in 40 seconds |
|
A Closer Look
Our GPS series emergency back up generator packages are ideal for use in: Data centers, Hospitals, Universities,office complexes, pharmaceuticals, and other facilities The GPS series start and attain full load in 40 seconds. These units are lighter in weight compared to competing diesel engine gen sets and are ideal for roof mounting. Units are dual fuel capable and can burn either liquid fuels or natural gas. natural gas fueled engines do not need diesel tanks on site freeing up business real estate for other purposes.
|
| Units Weights and Dimensions - US Customary Units (Switch To Metric) | |||||
| Electric Output | Dimension (L,W,H) | Weight | Exhaust Gas Temp. | Exhaust Gas Flow | |
| kWe | feet | lbs | °F | lbs/hr | |
| 400 | 9H X 4W X 6H | 1800 | 1094 | 16,380 | |
Fuel:
Standard configuration is Liquid fuel -; Dual fuel is an option with natural gas ; GT engine required gas inlet pressure is 220 psig
Note:
Performance based on 4 inch and 10 inch H2O intake / exhaust pressure losses
Based on a Sea level site
|
Standard Equipment
|