GPB06GPB06 Ideal for customers who demand reliable base loaded power generation in cogeneration applications - CHP from 500 to 600 kWs
The GPB06  is designed for base load power applications in cogeneration applications for customers who require from 500 to 600 kws.  It is ideal for use in: Hotels, Data centers,  Shopping malls, Hospitals, Universities,  Office complexes and apartment/ condos with CHP heating and cooling loads, pharmaceuticals, LNG Terminals, and other facilities .  This unit is light weight and is small in size when compared to comporable diesel engine generator sets.  With its small size and weight it is ideal for roof mounting.  This unit has dual fuel capability and can burn either natural gas or liquid fuels. 
A Closer Look

Our GPB units are dual fuel capable and can burn either natural gas or liquid fuel.   Generator designed for either 50 or 60 Hz applications.

 

 

GPB06 performance - US Customary Units (Switch To Metric)
Fuel Consumption Inlet air Temp. Electric Output steam production Co-gen efficiency
Btus/kwhr F kWe ton/ hr %
17,957 32 650 2.43 69.5
18,052 59 611 2.42 72.7
19,722 86 509 2.41 74.8
21,192 104 443 2.36 76.3


Fuel:
Natural gas fuel system is standard.  Backup is liquid fuel.

Note:
Performance based on  4 inch and 10 inch H2O  intake/exhaust pressure losses

Emissions -  50 ppm Nox,  80 ppm CO

Sea level site
Required gas pressure: 200 psig
Generator efficiency: 95%

Standard Equipment
Special Features
< Go to Top >